Wire Size Calculator

Most wire charts only look at amps. This calculator checks both things that decide a wire size: whether it can carry the current under NEC Table 310.16, and whether it keeps voltage drop under your target over the distance.

Built and maintained by Nouman Sabir AI search & SEO specialist Updated October 2026

  • 100% free
  • No sign-up
  • Runs in your browser, nothing is stored
A
V
ft
%

Recommended wire size

10 AWG

Copper, 2.33% drop

Sized for current

10 AWG

30.0 A at 75°C, rated 30 A

Sized for 3.0% drop

10 AWG

Over 75 ft

What decides the size

Current

Uses NEC Table 310.16 at 30°C with three or fewer current-carrying conductors, plus the 240.4(D) limits for 14, 12 and 10 AWG. It doesn't apply ambient or bundling derating. Have a licensed electrician confirm the final size.

Your inputs are saved in this browser only, so they're here when you come back.

Free contractor SEO audit

Want more calls for electrical work?

Send me your website and the areas you serve. I'll check your Maps rankings, service pages and AI visibility, and reply with the fixes that bring the most jobs.

Reviewed by Nouman Sabir
Top Rated on Upwork · 100% Job Success

No spam. Your details go only to me, never to a list.

How to use the Wire Size Calculator

  1. 1

    Enter the load in amps. If it runs for three hours or more (a continuous load), choose yes so it's sized at 125%.

  2. 2

    Enter the voltage, system type and one-way length, and your maximum voltage drop.

  3. 3

    Choose copper or aluminum and the terminal temperature rating. The recommended size is the larger of the ampacity size and the voltage-drop size.

Two checks decide the wire size

Ampacity keeps the wire from overheating. NEC Table 310.16 lists how many amps each size can carry, and the terminal rating decides which column you can use: 60°C for most equipment rated 100 A or less unless it's marked 75°C.

Voltage drop keeps the equipment working well. On a long run the ampacity size is often too small, which is why long circuits regularly need a wire one or two sizes larger than the ampacity chart says.

Common wire sizes by amps (copper, 75°C)

These are the usual sizes for short runs. Long runs and continuous loads often need the next size up.

  • 15 A: 14 AWG
  • 20 A: 12 AWG
  • 30 A: 10 AWG
  • 40 A: 8 AWG
  • 50 A: 8 AWG (6 AWG on 60°C terminals)
  • 60 A: 6 AWG
  • 100 A: 3 AWG
  • 200 A: 3/0 AWG

Frequently asked questions

What size wire do I need for 50 amps?

8 AWG copper on 75°C terminals or 6 AWG on 60°C terminals for a short run. For long runs, check voltage drop: 100 feet at 240 V usually calls for 6 AWG.

What size wire for a 30 amp circuit?

10 AWG copper. NEC 240.4(D) limits 10 AWG copper to a 30 A breaker.

Can I use aluminum wire?

Aluminum is common for feeders and service entrances. It needs a larger size than copper and terminals rated for aluminum (marked AL or AL/CU).

What is a continuous load?

A load expected to run at its maximum current for three hours or more, like EV chargers, water heaters and commercial lighting. The circuit is sized at 125% of that load.

Does this include derating?

No. It assumes a 30°C ambient and no more than three current-carrying conductors together. Hot attics, rooftops and bundled cables need derating. Have a licensed electrician confirm the final size.

More free SEO tools

All tools →
Contractors

Conduit Fill Calculator

Check NEC conduit fill for THHN wire and Cat6 or coax cable, and find the smallest conduit size.

Open the tool
Contractors

Voltage Drop Calculator

Find the voltage drop for a wire run and the smallest wire that keeps it under 3%.

Open the tool
Contractors

BTU Calculator

Estimate the AC tonnage and heating BTUs for a room or home by size, climate and insulation.

Open the tool

Free 30-min strategy call

No obligation

Book now