Voltage Drop Calculator

Enter the load, the one-way distance and the wire you plan to use. You get the voltage drop in volts and percent, the voltage left at the load and the smallest copper or aluminum wire that stays under your target.

Built and maintained by Nouman Sabir AI search & SEO specialist Updated October 2026

  • 100% free
  • No sign-up
  • Runs in your browser, nothing is stored
V

120, 208, 240, 277, 480, or 12/24 V DC

A
ft

From the panel to the load, not round trip.

%

3% for a branch circuit is the common design target.

Voltage drop

5.27%

6.32 V lost

Voltage at the load

113.7 V

Smallest wire for 3.0% or less

8 AWG

Copper

Max length at this size

57 ft

Before passing 3.0%

Over 5% total drop: motors run hot, LEDs flicker and equipment can fail early. Go up a size or shorten the run.

Uses the standard K-factor method (copper 12.9, aluminum 21.2) with NEC Chapter 9 Table 8 circular mils. Results are estimates for planning, not a stamped design.

Your inputs are saved in this browser only, so they're here when you come back.

Free contractor SEO audit

Want more calls for electrical work?

Send me your website and the areas you serve. I'll check your Maps rankings, service pages and AI visibility, and reply with the fixes that bring the most jobs.

Reviewed by Nouman Sabir
Top Rated on Upwork · 100% Job Success

No spam. Your details go only to me, never to a list.

How to use the Voltage Drop Calculator

  1. 1

    Choose single-phase (or DC) or three-phase, and enter the source voltage and the load in amps.

  2. 2

    Enter the one-way length from the panel to the load, the wire size and copper or aluminum.

  3. 3

    Check the drop against your target. If it's over, the calculator shows the smallest wire that brings it back under.

The voltage drop formula

For single-phase and DC circuits: VD = 2 × K × I × L ÷ CM. For three-phase circuits, replace the 2 with √3 (1.732). K is the resistivity of the conductor (12.9 for copper, 21.2 for aluminum), I is the current in amps, L is the one-way length in feet and CM is the wire's area in circular mils from NEC Chapter 9 Table 8.

Example: 16 A on 12 AWG copper (6,530 circular mils) over 100 feet at 120 V gives 2 × 12.9 × 16 × 100 ÷ 6,530 = 6.3 V, or 5.3%. Going up to 10 AWG brings it to 3.3%.

How much voltage drop is acceptable?

The NEC's informational notes recommend no more than 3% on a branch circuit and 5% in total across the feeder and branch circuit. They're recommendations, not requirements, but equipment makers and engineers design to them because low voltage makes motors run hot and electronics misbehave.

Low-voltage DC systems, like 12 V or 24 V lighting and solar, are far more sensitive: the same current loses a much bigger share of a small voltage, so runs need heavier wire.

Frequently asked questions

What is the maximum voltage drop allowed?

The NEC recommends 3% for a branch circuit and 5% total for feeder plus branch. Some jurisdictions and energy codes make these limits mandatory.

Do I use one-way or round-trip distance?

Enter the one-way distance. The formula's factor of 2 (single-phase) or √3 (three-phase) accounts for the return path.

Does aluminum wire have more voltage drop?

Yes, about 64% more than copper of the same size, which is why aluminum feeders are usually one or two sizes larger.

How do I reduce voltage drop?

Use a larger wire, shorten the run, raise the circuit voltage (240 V instead of 120 V) or split the load across circuits.

Is this accurate for long runs?

It uses the standard K-factor method that electricians use for planning. For engineered feeders, use impedance values from NEC Table 9, which include reactance and power factor.

More free SEO tools

All tools →
Contractors

Conduit Fill Calculator

Check NEC conduit fill for THHN wire and Cat6 or coax cable, and find the smallest conduit size.

Open the tool
Contractors

Wire Size Calculator

Get the right AWG wire size for the amps and distance, checked for ampacity and voltage drop.

Open the tool
Contractors

BTU Calculator

Estimate the AC tonnage and heating BTUs for a room or home by size, climate and insulation.

Open the tool